Room Thermostats, Zone Valves and ASHP efficiency - what we did
As part of our new build's design, the underfloor heating (UFH) was zoned and every room has a room thermostat. Section 8.2 of the Scottish Government's 2022 " Domestic Building Services Compliance Guide for Scotland " states in "Table 25: Recommended minimum standards for control of wet and electric underfloor heating systems" that "Each room should have its own thermostat, sensor or programmable thermostat." and we have exactly that. However, it is generally accepted that zoning is not a good setup to allow an air source heat pump (ASHP) to run efficiently. Zoning restricts how much of the UFH system is used to heat the house. As part of our ASHP installation, we specified two key things: the ASHP should have a controller in the main living area the UFH room thermostats should not be used to control the ASHP and that's what we have. Our Mitsubishi ASHP has a wired Mitsubishi controller in our main living area and the system is configured to ...